TinnerFlow logoTinnerFlow™
Fire/Smoke Dampers, Rated Assemblies & Access

Smoke Detector Location in Duct

Smoke detectors in ductwork must be located per code for proper detection.

Red / Stop And Verify2nd yearBatch 2

What You Might Be Looking At

smoke detector mounted in ductwork with sampling tubes extending into airstream

Apprentice words: smoke alarm in duct, detector in pipe, smoke sensor, duct detector

Trade terms: duct smoke detector, smoke detector in air duct, sampling tube

Check First

What code distance requirements apply?
Is detector on supply or return?
Are sampling tubes properly oriented?

What Not To Do

Don't install duct smoke detectors without checking NFPA 72 requirements. Don't sample from turbulent areas.

What can go wrong: Delayed smoke detection, false alarms, code violation, inspection failure, life safety risk

Better Foreman Question

For this duct smoke detector, what are the location requirements per NFPA 72? And is there adequate access for testing?

Open In Ask Foreman

Verify With

Reference type: NFPA 72, NFPA 90A, project specs

Source to verify: NFPA 72 National Fire Alarm Code, NFPA 90A, project fire alarm drawings

Safe wording: Detector placement and sampling tube requirements are controlled by fire alarm design, manufacturer instructions, code, and AHJ. Verify before cutting or mounting.

Search Related Field ChecksOpen Field ReferencesManufacturer Lookup