TinnerFlow logoTinnerFlow™
Equipment Connections

Outside Air Intake Clearance From Exhaust

Outside air intakes need separation from exhaust, plumbing vents, flues, loading docks, and contamination sources. This is not a guess field layout item.

Red / Stop And Verify3rdBatch 6

What This Helps With

Outside air intakes need separation from exhaust, plumbing vents, flues, loading docks, and contamination sources. This is not a guess field layout item.

Apprentice words: outside air intake clearance, exhaust near intake, louver separation, OA contamination

Common problem: OA intake or louver gets installed too close to exhaust discharge or contamination source.

Check First

Mechanical/site plan, code/AHJ requirements, equipment manufacturer, wind/weather exposure, and architectural louver location.

What Not To Do

Do not relocate intakes/exhausts in the field without approval. Do not assume distance is okay because it 'looks far enough.'

What can go wrong: OA intake or louver gets installed too close to exhaust discharge or contamination source.

Better Foreman Question

This outside air intake is near [exhaust/vent/loading area]. Who verifies required separation before we install/connect?

Open In Ask Foreman

Verify With

Source to verify: IMC, ASHRAE 62.1, project drawings, AHJ

Safe wording: Separation distances are code/design/AHJ controlled.

Search Related Field ChecksOpen Batch 6Ask Foreman