There is low airflow or no air at a diffuser after startup. What do I check first?
Airflow, Noise, Vibration & TAB Impactsyellow
Check install basics before blaming the unit: diffuser/grille installed, damper open/accessible, flex connected and not kinked, branch connected, fire/smoke damper open/reset as directed, and no blocked duct path.
This diffuser/register at [room/tag] has low/no airflow. I checked visible connection, damper access, and flex/branch condition. Do you want me to inspect upstream, hold for TAB, or check a specific damper/VAV?
Do not
Do not randomly move dampers, change controls, or tell the owner “the unit is bad” before install conditions are checked.
Why it matters
Low airflow often comes from a simple install condition: closed damper, kinked flex, disconnected branch, blocked access, or wrong device.