Fast answer

Check the run from durable architectural and layout references, then correct measured centerline, elevation, hanger alignment, and fitting rotation. Exposed retail duct is finished work; mechanically connected is not the same as visually complete.

What to check

  1. Check centerline and elevation with a laser or verified control points.
  2. Look along the run for rod plumb, hanger alignment, seam orientation, branch rotation, and diffuser alignment.
  3. Separate actual layout error from a dent, fitting distortion, or misleading sight line.
  4. Correct supports and alignment before final sealing or finish touch-up.

Do not

Do not chase appearance by randomly raising one hanger at a time without checking the full run.

Ask the foreman

“The exposed spiral is connected, but the centerline walks across the sales floor. I checked the laser and found two hangers off the control line. Do you want those supports reset before finish cleanup?”

Why it matters

Customer-facing duct can fail the visual punch even when every joint is technically connected.