Apprentice question

Verify first

Verify before you commit. Cheap to catch now.

Why do multi-section louvers need room for thermal movement?

Long aluminum louver banks expand and contract. Use the factory splice/expansion detail instead of bolting every section rigidly tight.

['A multi-section louver is not one solid chunk. Long aluminum runs need controlled movement at mullion joints, or heat can push the frames into each other and buckle the assembly.', 'Check the factory splice plates, gutter channels, expansion joint notes, and mullion alignment. The recovery is to disassemble the rigid joint, reset spacing per the submittal, and install sliding splice/gutter parts with flexible sealant where required.']

Equipment Connections: RTU, AHU, VAV, Fans & Louvers 3rd Year YELLOW

More in Equipment Connections: RTU, AHU, VAV, Fans & Louvers