Where should a fire damper sleeve sit in a rated wall opening?

Do not force retaining angles onto a sleeve that is too far in or out. Reposition the sleeve/damper per the manufacturer wall-opening detail so blades, sleeve, angles, and access all work.

['If the sleeve projects too far or sits too deep, the retaining angles may not seat, the damper may not sit correctly in the rated wall, and access/actuator clearances may be wrong.', 'The correction is to check the damper installation instructions, wall thickness, sleeve extension limits, blade location, and retaining angle requirements. Slide/reset the sleeve before firestop, drywall closure, or inspection if it is not positioned per the listed detail.']