Tell someone or document it before you close it up.
When pressure class changes connector requirements not recognized
Pressure class is not just a label - it can change the required connector, gauge, reinforcement, and sealing method. When duct changes pressure class mid-run, check the joint requirements before sealing or insulating.
Do not assume the same flange setup works after duct size or pressure class changes.
Check
Find the pressure-class note on the drawing, duct schedule, mechanical notes, or shop drawing for this section.
Identify where the pressure-class change occurs. Common places include equipment connections, VAV box inlets, distribution mains, branches, or transitions between systems.
Compare the connector you have installed with what the project spec, approved detail, shop standard, or SMACNA-based table requires for that pressure class.
Check whether reinforcement, tie rods, cross-angles, gasket, seal class, or a different flange/connector detail is required at the higher pressure section.
If the wrong connector or reinforcement appears to be installed, flag it before insulating or cover-up. Do not hide a pressure-class mismatch behind sealant or insulation.
Steps
Find the pressure-class note on the drawing, duct schedule, mechanical notes, or shop drawing for this section.
Identify where the pressure-class change occurs. Common places include equipment connections, VAV box inlets, distribution mains, branches, or transitions between systems.
Compare the connector you have installed with what the project spec, approved detail, shop standard, or SMACNA-based table requires for that pressure class.
Check whether reinforcement, tie rods, cross-angles, gasket, seal class, or a different flange/connector detail is required at the higher pressure section.
If the wrong connector or reinforcement appears to be installed, flag it before insulating or cover-up. Do not hide a pressure-class mismatch behind sealant or insulation.
Say this to your foreman
The duct changes pressure class at [location]. I have [connector type] installed, but this section may require [different connector/reinforcement/seal detail]. Can you confirm before I seal and insulate?