Pre-Fire-Damper Inspection Walk
Use before AHJ/fire damper inspection to check access, labels, blade path, and corrections.
Fire/smoke/combination damper inspection is scheduled or ceiling/wall closure is close.
Stop if
- Ask when access, label, actuator, blade path, sleeve, retaining angle, or correction owner is unclear.
Watch out
- Do not cover or close ceiling over unknown damper access.
- Do not force painted/seized access doors without direction.
- Do not claim corrected without photos/recheck if inspection is involved.
Check
- Damper label
- Access open/closed
- Blade path concern
- Wide room/grid
Steps
- Walk each damper location like the inspector will ask to see it open, visible, and documented.
- List each damper by room/grid/tag.
- Verify access panel exists, opens, and is large enough to inspect/service.
- Confirm UL/listing label and damper ID are visible and not covered.
- Check actuator/handle/control side clearance.
- Check blade path for screws, liner, insulation, debris, or duct edges.
- Photo and assign owner for each not-ready item.