You need a minimum of 3 to 5 straight, uninterrupted duct diameters of straight round pipe before entering the VAV box inlet. If you place an elbow or a sharp transition directly on the inlet collar, the air will spin turbulently, causing the flow sensor tubes inside the VAV inlet to read incorrectly, ruining the system balance.
['You need a minimum of 3 to 5 straight, uninterrupted duct diameters of straight round pipe before entering the VAV box inlet. If you place an elbow or a sharp transition directly on the inlet collar, the air will spin turbulently, causing the flow sensor tubes inside the VAV inlet to read incorrectly, ruining the system balance.']
how many duct diameters of straight pipe do i need before the inlet of a vav box?