How do I install a retaining angle on a fire damper in a masonry wall?

Position the damper sleeve centered in the wall penetration. Place the pre-formed steel retaining angles (1\frac{1}{2}\text{ in} \times 1\frac{1}{2}\text{ in} minimum) tight against the masonry surface on all four sides of the sleeve perimeter. Fasten the angles directly to the damper sleeve using approved screws or welds spaced per manufacturer instructions. Do not anchor the angle directly into the masonry wall.

['Position the damper sleeve centered in the wall penetration. Place the pre-formed steel retaining angles (1\\frac{1}{2}\\text{ in} \\times 1\\frac{1}{2}\\text{ in} minimum) tight against the masonry surface on all four sides of the sleeve perimeter. Fasten the angles directly to the damper sleeve using approved screws or welds spaced per manufacturer instructions. Do not anchor the angle directly into the masonry wall. ']

Airflow, Noise, Vibration & TAB 2nd Year RED

Stop if

Check

Steps

Say this to your foreman

how do i install a retaining angle on a fire damper in a masonry wall?