Fire damper retaining angles are screwed into the wall framing
Fire damper retaining angles are part of a listed install detail. If they are fastened to the wrong thing, stop and verify the manufacturer/listing before cover or inspection.
Compare installed fasteners to the manufacturer/listing detail.
Check whether framing, drywall, or wall closure is pinning the sleeve/angles.
Verify blade movement and access after correcting fasteners.
Take photos for inspection/closeout before cover.
Say this to your foreman
The fire damper retaining angles at [location] are fastened into wall framing. I checked the damper tag and install sheet. Do you want those fasteners removed/reinstalled per the listed detail before cover?