Duct hits a rated wall at a 45-degree angle and the fire damper cannot sit square
Do not angle a fire/smoke damper through a rated wall unless the listed assembly specifically allows it. Square the duct to the wall with approved fittings before the damper sleeve.
Stop if
- The duct approaches the rated wall at a 45 and the damper will not sit square in the sleeve. I stopped before cutting/setting it. Do you want an upstream offset to square the duct to the wall or a detailer RFI?
Watch out
- Do not install a fire/smoke damper cocked at an angle through a rated wall because the duct line came in crooked.
Check
- Confirm the wall rating and damper type.
- Check manufacturer installation instructions for allowed orientation.
- Verify sleeve is square to the wall plane.
- Lay out upstream elbows/offsets to enter perpendicular if required.
- Do not cover until access, sleeve, angles, and firestop are accepted.
Steps
- Confirm the wall rating and damper type.
- Check manufacturer installation instructions for allowed orientation.
- Verify sleeve is square to the wall plane.
- Lay out upstream elbows/offsets to enter perpendicular if required.
- Do not cover until access, sleeve, angles, and firestop are accepted.