An elbow is installed directly on a VAV inlet

A hard elbow at the VAV inlet can make the airflow sensor read dirty, uneven air. Check the VAV manufacturer/install detail and bring options like a straight spool, box shift, or approved inlet fitting before TAB/startup.

Equipment Connections: RTU, AHU, VAV, Fans & Louvers 2nd Year YELLOW

Watch out

Check

Steps

Say this to your foreman

VAV [tag] has a hard elbow right at the inlet. I checked the tag and available straight length. Do you want me to add a straight spool, shift the box, use an approved inlet fitting, or hold for detailer/TAB direction?