There is a rigid brace crossing the canvas connector at [unit/location]. It is locking out the flex break. Do you want separate restraints on the duct side and equipment side?
Watch out
Do not tie the equipment and duct solid across a flexible connector.
Check
Confirm the brace physically connects both sides of the flex connector.
Check whether vibration is transferring across the joint.
Verify independent seismic/vibration restraint for duct and equipment.
Do not remove required bracing without a replacement layout.
Coordinate with foreman/inspector if the brace was already tagged.
Steps
Confirm the brace physically connects both sides of the flex connector.
Check whether vibration is transferring across the joint.
Verify independent seismic/vibration restraint for duct and equipment.
Do not remove required bracing without a replacement layout.
Coordinate with foreman/inspector if the brace was already tagged.
Say this to your foreman
There is a rigid brace crossing the canvas connector at [unit/location]. It is locking out the flex break. Do you want separate restraints on the duct side and equipment side?