A 45-degree branch enters directly into a VAV inlet and causes bad readings
A VAV inlet needs stable air entering the sensor area. An angled short entry can spin the air and make the box read wrong.
Stop if
- VAV [number] has a 45-degree entry right at the inlet and TAB readings may be unstable. I checked the inlet path. Do you want a straight rigid spool added before the box?
Watch out
- Do not slam an angled fitting directly onto a VAV inlet and expect stable CFM readings.
Check
- Check if an elbow or 45 enters directly at the VAV collar.
- Look for short flex or offset right at the inlet.
- Confirm airflow arrow and sensor tubing are correct.
- Ask TAB/foreman if readings are unstable.
- Provide straight rigid inlet run where the project/detail requires it.
Steps
- Check if an elbow or 45 enters directly at the VAV collar.
- Look for short flex or offset right at the inlet.
- Confirm airflow arrow and sensor tubing are correct.
- Ask TAB/foreman if readings are unstable.
- Provide straight rigid inlet run where the project/detail requires it.