Grease duct through rated shaft
Fire-rated enclosure penetration
The approved design, adopted code, qualified procedure, and exact manufacturer instructions control this installation.
Before you start
- Grease duct is a fire/life-safety system. Verify the approved design, adopted code, hood and fan requirements, listed enclosure or shaft details, and inspection hold points before fabrication or installation.
- Confirm the rated shaft or listed enclosure assembly, duct clearances, supports, penetrations, access assemblies, firestop interfaces, and inspection sequence.
- Use the approved tested or listed details for the exact wall, floor, shaft, and duct system.
- Verify that supports are structural and independent of shaft walls and enclosure materials.
- Coordinate aligned access openings through both the grease duct and enclosure.
Tools and materials
Grease-duct system, approved shaft or listed enclosure components, independent structural supports, compatible penetration and firestop components, listed access assemblies, layout tools, inspection light, labels, and manufacturer or tested-assembly instructions.
Lay it out
- Lay out duct, supports, shaft clearances, access doors, and floor or wall penetrations together.
- Keep the duct centered and prevent combustible construction or unrelated services from entering the required clearance zone.
- Sequence the work so grease-duct joints can be inspected before shaft or enclosure closure.
Set and support it
- Install independent structural supports before enclosure work closes access.
- Do not attach duct supports to shaft liner, fire-wrap, gypsum enclosure, or other nonstructural rated components unless the approved assembly specifically shows it.
- Maintain the required gap around the duct and penetrations.
Make the connection
- 1
Install and inspect the grease-duct section and liquid-tight joint.
- 2
Set structural support and verify the duct does not bear on the shaft or penetration.
- 3
Install the approved shaft or listed enclosure components around the duct.
- 4
Complete penetrations using the compatible tested or listed detail.
- 5
Align enclosure access with the grease-duct access door.
- 6
Inspect continuity at joints, corners, supports, and penetrations.
- 7
Photograph and document the assembly before concealment.
Check the install
- The enclosure or shaft is continuous and matches the approved assembly.
- The duct remains independently supported and properly separated from shaft construction.
- Access doors align and can be used for cleaning.
- Penetrations and firestop interfaces use approved compatible details.
- No combustible or unrelated material intrudes into the protected space.
Common mistakes
- Treating fire-wrap, shaft liner, and field-built shafts as interchangeable.
- Attaching supports to nonstructural enclosure material.
- Closing the shaft before duct-joint inspection.
- Misaligning enclosure access with the grease-duct door.
Stop and ask
Stop if the field condition differs from the tested or listed assembly, support attachment is unclear, access doors do not align, or a penetration detail is missing or incompatible.